Production Standards:
JB/T10491, GB/T9330-2020, GB/T12706.1-2020, and other relevant cable standards.
Usage Conditions:
1. Rated voltage U./U: 450/750V, 0.6/1kV.
2. Maximum conductor temperature during normal operation: 90℃ (omitted); 105℃-105℃; 125℃-125℃.
3. Cable laying temperature not lower than 0℃.
4. Minimum allowable bending radius during cable laying:
For unarmored cables, the allowable bending radius should not be less than 5 times the cable's outer diameter.
For armored cables, it should not be less than 12 times the cable's outer diameter.
And corresponding product standard requirements.
5. Suitable for applications requiring flame retardancy.
Product Model Name
| Core Count | Voltage Rating (kV) | Cross-section (mm²) |
| 1-core | 0.6/1 kV and below | 1.5 ~ 240 |
| 2-core | 0.6/1 kV and below | 1.5 ~ 240 |
| 3-core | 0.6/1 kV and below | 1.5 ~ 240 |
| 3 large + 1 core | 0.6/1 kV and below | 1.5 ~ 240 |
| 4 equal cores | 0.6/1 kV and below | 1.5 ~ 240 |
| 5 equal cores | 0.6/1 kV and below | 1.5 ~ 240 |
| 3 large + 2 small cores | 0.6/1 kV and below | 1.5 ~ 240 |
| 4 large + 1 small core | 0.6/1 kV and below | 1.5 ~ 240 |
Note: Flame-retardant cables of type WDZB and WDZA; fire-resistant cables of type WDZCN, WDZBN, and WDZAN can be supplied according to user requirements.
Wire and Cable Specification Range
| Model | English Name |
| WDZC-BYJ | Cross-linked polyolefin insulated flexible wires |
| WDZC-BYJ-105 | Cross-linked polyolefin insulated flexible wires |
| WDZC-BYJ(F) | Copper core radiation cross-linked low-smoke halogen-free flame-retardant polyolefin insulated eco-friendly wires |
| WDZC-BYJ(F)R | Copper core radiation cross-linked low-smoke halogen-free flame-retardant polyolefin insulated eco-friendly flexible wires |
| WDZC-BYJ(F)YB | Copper core radiation cross-linked low-smoke halogen-free flame-retardant polyolefin insulated and sheathed flat eco-friendly cables |
| WDZCN-BYJ(F) | Copper core radiation cross-linked low-smoke halogen-free flame-retardant polyolefin insulated fire-resistant eco-friendly wires |
| WDZC-KYJ(F)Y | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed control cables |
| WDZC-KYJ(F)Y | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed flexible control cables |
| RWDZC-KYJ(F)Y23 | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed steel tape armored control cables |
| WDZC-KYJ(F)YP | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed copper wire braided shielded control cables |
| WDZC-KYJ(F)YP2 | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed copper tape shielded control cables |
| WDZCN-KYJ(F)Y | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed fire-resistant control cables |
| WDZC-YJ(F)Y | Copper core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)LY | Aluminum core radiation cross-linked polyethylene insulated low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)Y23 | Copper core radiation cross-linked polyethylene insulated steel tape armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)LY23 | Aluminum core radiation cross-linked polyethylene insulated steel tape armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)Y33 | Copper core radiation cross-linked polyethylene insulated fine steel wire armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)LY33 | Aluminum core radiation cross-linked polyethylene insulated fine steel wire armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)Y43 | Copper core radiation cross-linked polyethylene insulated thick steel wire armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
| WDZC-YJ(F)LY43 | Aluminum core radiation cross-linked polyethylene insulated thick steel wire armored low-smoke halogen-free flame-retardant polyolefin sheathed power cables |
Main Electrical Performance
1. Conductor DC resistance at 20℃ conforms to GB/T3956.
2. Maximum elongation under cable insulation load is 175%, and maximum permanent elongation after cooling is 15%.
3. Other performance indicators conform to the technical requirements of the corresponding product standards.